Current Location:Home>Product> Secondary UD cable

Multi URD cable

 600 Volt. Aluminum AlloyConductorCross-Linked Polyethylene (XLPE) Insulation Multicore Conductor Underground Service And Secondary Distribution Cable

APPLICATIONS

Secondary UD cable with 1350-H19 Aluminum conductor suitable for use in underground service and secondary distribution, Neutrals are identified by triple yellow extruded stripe,Secondary UD is permitted for 600 volt or less applications,either direct burial or in ducts.

STANDARDS

Secondary UD complies with the following:

ASTM B230,B231

UL 854

ICEA S-105-692

CONSTRUCTION

Conductor

Stranded compressed 1350-H19 aluminum

Insulation

cross-linked polyethylene (XLPE) insulation

TECHNICAL PARAMETER LIST

Code Word

Phase Conductors

Neutral Conductors

Single phase

O.D. (mils)

Complete cable O.D. (mils)

Approx.

Weight per

1000' (lbs)

Allowable Ampacity

Size

(AWG or kcmil)

Number of

Strands

Insulation Thickness

(mils)

Size

(AWG or kcmil)

Number of

Strands

Insulation Thickness

(mils)

Direct Burial

In

Ducts

Duplex Conductor Secondary Type URD

Bard

8

7

60

8

7

60

262

524

70

70

55

Clafin

6

7

60

6

7

60

299

596

90

95

70

Delgado

4

7

60

4

7

60

345

690

127

125

90

Everett

2

7

60

2

7

60

403

808

187

187

100

Triplex Conductor Secondary Type URD

Erskine

6

7

60

6

7

60

299

644

140

95

70

Vassar

4

7

60

4

7

60

345

745

200

125

90

Stephens

2

7

60

4

7

60

403

842

260

165

120

Ramapo

2

7

60

2

7

60

403

870

285

165

120

Brenau

1/0

9

80

2

7

60

520

1064

399

215

160

Bergen

1/0

9

80

1/0

9

80

520

1133

455

215

160

Converse

2/0

11

80

1

9

80

565

1174

490

245

180

Hunter

2/0

11

80

2/0

11

80

565

1228

550

245

180

Hollins

3/0

17

80

1/0

9

80

610

1275

600

280

205

Rockland

3/0

17

80

3/0

17

80

610

1302

660

280

205

Sweetbriar

4/0

18

80

2/0

11

80

658

1390

725

315

240

Monmouth

4/0

18

80

4/0

18

80

658

1458

812

315

240

Pratt

250

26

95

3/0

17

80

732

1581

853

345

265

Wesleyan

350

37

95

4/0

18

80

831

1795

1118

415

320

Holyoke

500

37

95

300

37

95

980

1980

1545

495

395

Rider

500

37

95

350

37

95

980

2117

1598

495

395

 

 

 

 

Code Word

Phase Conductors

Neutral Conductors

Single phase

O.D. (mils)

Complete cable O.D. (mils)

Approx.

Weight per

1000' (lbs)

Allowable Ampacity

Size

(AWG or kcmil)

Number of

Strands

Insulation Thickness

(mils)

Size

(AWG or kcmil)

Number of

Strands

Insulation Thickness

(mils)

Direct Burial

In

Ducts

Quadruplex Conductor Secondary Type URD

Tulsa

4

7

60

4

7

60

345

833

255

119

95

Dyke

2

7

60

4

7

60

403

938

345

153

115

Wittenberg

2

7

60

2

7

60

403

973

371

153

115

Notre Dame

1/0

9

80

2

7

60

512

1188

534

200

150

Purdue

1/0

9

80

1/0

9

80

512

1236

589

200

150

Syracuse

2/0

11

80

1

9

80

555

1316

657

225

170

Lafayette

2/0

11

80

2/0

11

80

555

1340

713

225

170

Swarthmore

3/0

17

80

1/0

9

80

603

1440

798

250

195

Davidson

3/0

17

80

3/0

17

80

603

1456

868

250

195

Wake Forest

4/0

18

80

2/0

11

80

658

1540

971

290

225

Earlham

4/0

18

80

4/0

18

80

658

1588

1062

290

225

Slippery Rock

350

30

95

4/0

18

80

831

2006

1527

385

305

Wofford

500

37

95

350

30

95

980

2366

2179

465

370

Ampacity:90°C conductor temperature, 20°C ambient temperature, RHO factor 90, 100% load factor for three conductor triplexed.

 

 

NOTE: Other conductor sizes are available upon request.